Gases in TransformerOil AnalysisApplication Notes #283028Transformer Oil Gas Analysis with the Bruker TOGAAnalyzer equipped with the Bruker Headspace Sampler.Insulating fluids, generally mineral oils, are used intransformers. Under normal, mild conditions there isAs a result, a portion of a gas dissolved...
Klíčová slova
oil, oiltransformer, transformerbruker, brukergases, gasestoga, togastripper, stripperfill, filloff, offgas, gasbypass, bypassrepeatability, repeatabilitytcd, tcdschaffer, schafferextracted, extracteddissolved
Transformer Oil Gas Analysis via Headspace Sampling (ASTM D3612)AN0030Application NoteINTRODUCTIONTable 1 details the analytes of interest obtained froman injection of a commercial oil standard.Insulating fluids, generally mineral oils, are used intransformers. Under normal, mild conditions, there isvery little decomposition. However,...
Klíčová slova
oil, oilscion, scionrepeatability, repeatabilitytransformer, transformeroff, offfill, fillbypass, bypassonto, ontoheadspace, headspaceseries, seriesextraction, extractiontcd, tcddissolved, dissolvedporous, porousmethaniser
TOGA
|Thermo Fischer Scientific|Brožury a specifikace
SpecificationsStandard methods:ASTM D3612 part CFully automated Transformer Oil Gas AnalyserConfiguration:One channel instrument based on Thermo Trace 1300 GC or CompactGC,According to ASTM D 3612cPerforms better than ASTM 3612c requirementsusing microTCD, methaniser and FID.Automated injection, closed loop principle, using:Small footprint- Teledyne...
Klíčová slova
toga, togamethaniser, methaniserinstantconnect, instantconnecttcd, tcdfid, fidtransformer, transformeranalyser, analyseriec, iecautosampler, autosamplergas, gasloop, loopacetylene, acetylenefootprint, footprintoil, oilclosed
NOTICE: This document contains references to Varian.Please note that Varian, Inc. is now part of AgilentTechnologies. For more information, go towww.agilent.com/chem.Application Note SI-01298Analysis of Dissolved Gas in Transformer Oil by Gas Chromatography using a Stripper ColumnCoen Duvekot, Inze Bos and...
Klíčová slova
stripper, strippervent, ventgases, gasestoga, togamin, minchannel, channeldissolved, dissolvedporabond, porabondmethanizer, methanizeroven, ovenoil, oilgas, gasfigures, figurescolumn, columnflushed
 

Podobná PDF

Toggle
Gases in TransformerOil AnalysisApplication Notes #283028Transformer Oil Gas Analysis with the Bruker TOGAAnalyzer equipped with the Bruker Headspace Sampler.Insulating fluids, generally mineral oils, are used intransformers. Under normal, mild conditions there isAs a result, a portion of a gas dissolved...
Klíčová slova
oil, oiltransformer, transformerbruker, brukergases, gasestoga, togastripper, stripperfill, filloff, offgas, gasbypass, bypassrepeatability, repeatabilitytcd, tcdschaffer, schafferextracted, extracteddissolved
Transformer Oil Gas Analysis via Headspace Sampling (ASTM D3612)AN0030Application NoteINTRODUCTIONTable 1 details the analytes of interest obtained froman injection of a commercial oil standard.Insulating fluids, generally mineral oils, are used intransformers. Under normal, mild conditions, there isvery little decomposition. However,...
Klíčová slova
oil, oilscion, scionrepeatability, repeatabilitytransformer, transformeroff, offfill, fillbypass, bypassonto, ontoheadspace, headspaceseries, seriesextraction, extractiontcd, tcddissolved, dissolvedporous, porousmethaniser
TOGA
|Thermo Fischer Scientific|Brožury a specifikace
SpecificationsStandard methods:ASTM D3612 part CFully automated Transformer Oil Gas AnalyserConfiguration:One channel instrument based on Thermo Trace 1300 GC or CompactGC,According to ASTM D 3612cPerforms better than ASTM 3612c requirementsusing microTCD, methaniser and FID.Automated injection, closed loop principle, using:Small footprint- Teledyne...
Klíčová slova
toga, togamethaniser, methaniserinstantconnect, instantconnecttcd, tcdfid, fidtransformer, transformeranalyser, analyseriec, iecautosampler, autosamplergas, gasloop, loopacetylene, acetylenefootprint, footprintoil, oilclosed
NOTICE: This document contains references to Varian.Please note that Varian, Inc. is now part of AgilentTechnologies. For more information, go towww.agilent.com/chem.Application Note SI-01298Analysis of Dissolved Gas in Transformer Oil by Gas Chromatography using a Stripper ColumnCoen Duvekot, Inze Bos and...
Klíčová slova
stripper, strippervent, ventgases, gasestoga, togamin, minchannel, channeldissolved, dissolvedporabond, porabondmethanizer, methanizeroven, ovenoil, oilgas, gasfigures, figurescolumn, columnflushed
 

Mohlo by Vás zajímat

Utilising unique TOF-MS technology and hydrogen carrier gas for fast GC-MS to produce robust, high quality, library comparable mass spectral data

Postery
| 2022 | LECO
Instrumentace
GC/MSD, GC/TOF
Výrobce
LECO
Zaměření
---

Determination of BTEX and volatile organic compounds (VOCs) in drinking water by GC-MS/MS coupled to static headspace and solid-phase microextraction sampling

Aplikace
| 2022 | Thermo Fischer Scientific
Instrumentace
GC/MSD, GC/MS/MS, HeadSpace, GC/QQQ
Výrobce
Thermo Fischer Scientific
Zaměření
Životní prostředí

Analysis of Trace Perfluorinated and Polyfluorinated Organic Vapors in Air

Aplikace
| 2022 | Agilent Technologies
Instrumentace
GC/MSD, Termální desorpce, GC/SQ
Výrobce
Agilent Technologies, Markes
Zaměření
Životní prostředí

Analysis of Acetaldehyde and Limonene in Recycled PET Using an HS-GC/MS System

Aplikace
| 2022 | Shimadzu
Instrumentace
GC/MSD, HeadSpace, GC/SQ
Výrobce
Shimadzu
Zaměření
Průmysl a chemie

Analysis of Heavy Fuel Oil Using Multi-Mode Ionization

Aplikace
| 2022 | LECO
Instrumentace
GCxGC, GC/MSD, GC/HRMS, GC/TOF
Výrobce
LECO
Zaměření
Průmysl a chemie
 

Mohlo by Vás zajímat

Utilising unique TOF-MS technology and hydrogen carrier gas for fast GC-MS to produce robust, high quality, library comparable mass spectral data

Postery
| 2022 | LECO
Instrumentace
GC/MSD, GC/TOF
Výrobce
LECO
Zaměření
---

Determination of BTEX and volatile organic compounds (VOCs) in drinking water by GC-MS/MS coupled to static headspace and solid-phase microextraction sampling

Aplikace
| 2022 | Thermo Fischer Scientific
Instrumentace
GC/MSD, GC/MS/MS, HeadSpace, GC/QQQ
Výrobce
Thermo Fischer Scientific
Zaměření
Životní prostředí

Analysis of Trace Perfluorinated and Polyfluorinated Organic Vapors in Air

Aplikace
| 2022 | Agilent Technologies
Instrumentace
GC/MSD, Termální desorpce, GC/SQ
Výrobce
Agilent Technologies, Markes
Zaměření
Životní prostředí

Analysis of Acetaldehyde and Limonene in Recycled PET Using an HS-GC/MS System

Aplikace
| 2022 | Shimadzu
Instrumentace
GC/MSD, HeadSpace, GC/SQ
Výrobce
Shimadzu
Zaměření
Průmysl a chemie

Analysis of Heavy Fuel Oil Using Multi-Mode Ionization

Aplikace
| 2022 | LECO
Instrumentace
GCxGC, GC/MSD, GC/HRMS, GC/TOF
Výrobce
LECO
Zaměření
Průmysl a chemie
Další projekty
Sledujte nás
Další informace
WebinářeO násKontaktujte násPodmínky užití

LabRulez s.r.o. Všechna práva vyhrazena.